top of page
RXM2LB2BD miniature, Harmony Electromechanical Relays, 5A, 2CO, with LED, 24V DC

RXM2LB2BD miniature, Harmony Electromechanical Relays, 5A, 2CO, with LED, 24V DC

$8.00Price

RXM miniature relays are part of Harmony Electromechanical Relays. This is a plug in relay to be mounted on a RXZE socket. It is a 2 C/O relay with current rating of 5A, control circuit voltage of 24 V DC. It also offers a mechanical indicator where an orange flag indicates the relay contact status. The product is IP40 and has a transparent cover allowing operator to visually inspect the status of contacts. A green LED on the front will illuminate when the relay is on. Status display with LED: clearly signal both in the day and night. Its design is fit for industrial machines, packaging, textile, HVAC, automation control panels, low/medium voltage switchgear, motor controls, PLC Interfaces, power supplies, building or medical equipment, lighting controls. It is a green premium product and conforms to international standard and certifications like IEC, CE. RXM relay need to be used with a RXZE socket RXZE1M2C. To protect against vibrations, metal clamp RXZ410/RXZ420 can be added to the socket. It is sold in lots of 10 and reference includes relay only. The RXMLB plug-in relays are a series of industrial plug-in relays designed for both simple and complex automation systems and available with 2 CO (5A), 4 CO (3A) contacts.

  • Specifications

    Main
    Range of Product Harmony Electromechanical Relays
    Coil interference suppression Without
    Series name Miniature
    Product or Component Type Plug-in relay
    Device short name RXM
    Contacts type and composition 2 C/O
    [Ithe] conventional enclosed thermal current 5 A -40…131 °F (-40…55 °C)
    Complementary
    Contact operation Standard
    [Uc] control circuit voltage 24 V DC
    Status LED With
    Control Type Without push-button
    [Uimp] rated impulse withstand voltage 4 kV 1.2/50 µs IEC 61810-7
    [Ie] rated operational current 5 A AC-1/DC-1) NO IEC
    2.5 A AC-1/DC-1) NC IEC
    1 A 28 V DC-13) NO
    Minimum switching capacity 25 mW subject to switching frequency, environment or expected reliability level etc
    Operating time 20 ms between coil de-energisation and making of the Off-delay contact
    20 ms between coil energisation and making of the On-delay contact
    CAD overall width 0.83 in (21 mm)
    CAD overall height 1.06 in (27 mm)
    CAD overall depth 1.81 in (46 mm)
    Minimum switching current 5 mA subject to switching frequency, environment or expected reliability level etc
    Minimum switching voltage 5 V subject to switching frequency, environment or expected reliability level etc
    Rated operational voltage limits 19.2...26.4 V DC
    [Ui] rated insulation voltage 250 V IEC
    Maximum switching voltage 250 V AC
    28 V DC
    Drop-out voltage threshold >= 0.1 Uc DC
    Load current 5 A 250 V AC
    5 A 28 V DC
    Maximum switching capacity 1250 VA AC
    140 W DC
    Average resistance 640 Ohm at 73 °F (23 °C) +/- 10 %
    Average coil consumption 0.9 W, DC
    Mechanical durability 10000000 cycles
    Electrical durability 100000 cycles for resistive load
    50000 cycles, 1 A at 28 V, DC-13 NO
    Safety reliability data B10d = 100000
    Operating rate <= 1200 cycles/hour under load
    <= 18000 cycles/hour no-load
    Utilisation coefficient 20 %
    Dielectric strength 2000 V AC between coil and contact with basic insulation
    2000 V AC between poles with basic insulation
    1000 V AC between contacts with micro disconnection
    Protection category RT I
    Pollution degree 3
    Operating position Any position
    Test levels Level A group mounting
    Sale per indivisible quantity 10
    Contacts material Silver alloy (Ag/Ni)
    Net Weight 0.07 lb(US) (0.032 kg)
    Environment
    IP degree of protection IP40 conforming to IEC 60529
    Standards IEC 61810-1 (iss. 2)
    CE
    Ambient Air Temperature for Storage -40…185 °F (-40…85 °C)
    Vibration resistance 3 gn +/- 1 mm 10…50 Hz)operating IEC 60068-2-6
    6 gn +/- 1 mm 10…50 Hz)not operating IEC 60068-2-6
    Shock resistance 30 gnnot operating IEC 60068-2-27
    10 gnin operation IEC 60068-2-27
bottom of page