METSEPM5650 power meter, 2 ethernet, up to 63th Harmonic
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current plus an advanced waveform capture with sag and swell detection. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 3.03 inches (77 millimetres), height 3.78 inches (96 millimetres) and product weight 15.9 onces (450 g).
Specifications
Main Range PowerLogic Product name PowerLogic PM5000 device short name PM5650 Product or Component Type Power meter Complementary Power quality analysis Up to the 63rd harmonic
waveform capture
voltage sag and swell detectionMetering type Measured neutral current
Calculated ground currentDevice Application Gateway
WAGES metering
Power monitoring
Multi-tariffType of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive powersupply voltage 100...300 V DC
90...528 V AC 45...65 HzNetwork Frequency 60 Hz
50 HzLine Rated Current 1 A
5 Atype of network 3P + N
3P
1P + NMaximum power consumption in VA 16 VA 480 V Ride-through time 35 ms 120 V AC typical
129 ms 230 V AC typical
50 ms 125 V DC typicalDisplay Type Monochrome graphic LCD Display Resolution 128 x 128 pixels Sampling rate 128 samples/cycle Measurement current 50…10000 mA Analogue input type Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)Measurement voltage 20…400 V AC 45...65 Hz between phase and neutral
20…828 V AC 45...65 Hz between phasesFrequency measurement range 45…65 Hz Number of inputs 4 digital Measurement accuracy Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Active energy +/- 0.2 %
Reactive energy +/- 1 %
Active power +/- 0.2 %
Voltage +/- 0.1 %
Power factor +/- 0.005
Current +/- 0.15 %
Reactive power +/- 1 %Accuracy class Class 0.2S active energy IEC 62053-22 Number of Outputs 2 digital Information displayed Tariff 8) Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
JBUS
Modbus TCP/IP 10/100 Mbit/s 2500 V
Ethernet Modbus TCP/IP daisy chain
BACnet IP
DNP3 over ethernetCommunication port support RS485
ETHERNETcommunication gateway Ethernet/serial data recording Event logs
Maintenance logs
Min/max of instantaneous values
Data logs
Alarm logs
Time stampingMemory capacity 1.1 MB Web services Alarm notification by e-mail
Web server
Diagnostic via predefined web pages
Real time viewing of dataEthernet service SNTP client
SNMP-TrapsConnections - terminals Voltage circuit screw terminal block4
Control circuit screw terminal block2
Current transformer screw terminal block6
RS485 link screw terminal block4
Digital input screw terminal block8
Digital output screw terminal block4
Ethernet network RJ45 connector2Mounting Mode Flush-mounted Mounting support Framework Standards EN 50470-3
IEC 61557-12:2015
IEC 62053-22:2020
IEC 62053-24
IEC 60529
EN 50470-1
UL 61010-1
IEC 62053-23:2020
IEC 62052-11:2020
IEC 62052-31:2015Product certifications CE IEC 61010-1
CULus UL 61010-1Width 3.78 in (96 mm) Depth 2.83 in (72 mm) Height 3.78 in (96 mm) Net Weight 15.87 oz (450 g) Environment Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
Surge immunity test level 4 conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11IP degree of protection Display IP54 IEC 60529
Rear IP30 IEC 60529Relative humidity 5…95 % 122 °F (50 °C) non-condensing Pollution degree 2 Ambient air temperature for operation -13…158 °F (-25…70 °C) Ambient Air Temperature for Storage -40…185 °F (-40…85 °C) Operating altitude <= 9842.52 ft (3000 m)