top of page
METSEPM5650 power meter, 2 ethernet, up to 63th Harmonic

METSEPM5650 power meter, 2 ethernet, up to 63th Harmonic

SKU: 3606489869717
$890.00Price

 

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.2S accuracy per IEC 62053-22 standard and 128 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 63rd Harmonic. Include 1.1 MegaBytes of memory for up to 14 selectable parameters with configurable interval and duration. This meter also feature the direct monitoring of neutral current plus an advanced waveform capture with sag and swell detection. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 480 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 20 to 690 VAC at 45 to 65 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 45 to 65 Hz. Communication protocol are Modbus RTU and ASCII 2 wires with RS485 port support plus Modbus TCP/IP, Ethernet/IP and BACnet/IP based on 10/100 Mbit/s, daisy chain Ethernet with RJ45 port support. The embedded communication capabilities allow the support of the DNP 3.0 protocol, the access to an onboard web server and a Serial to Ethernet gateway. The meter also has four digital inputs with WAGES support and two digital outputs. There are 52 configurable alarms and it supports eight tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 3.03 inches (77 millimetres), height 3.78 inches (96 millimetres) and product weight 15.9 onces (450 g).

Only 1 left in stock
  • Specifications

    Main
    Range PowerLogic
    Product name PowerLogic PM5000
    device short name PM5650
    Product or Component Type Power meter
    Complementary
    Power quality analysis Up to the 63rd harmonic
    waveform capture
    voltage sag and swell detection
    Metering type Measured neutral current
    Calculated ground current
    Device Application Gateway
    WAGES metering
    Power monitoring
    Multi-tariff
    Type of measurement Current
    Voltage
    Frequency
    Power factor
    Energy
    Active and reactive power
    supply voltage 100...300 V DC
    90...528 V AC 45...65 Hz
    Network Frequency 60 Hz
    50 Hz
    Line Rated Current 1 A
    5 A
    type of network 3P + N
    3P
    1P + N
    Maximum power consumption in VA 16 VA 480 V
    Ride-through time 35 ms 120 V AC typical
    129 ms 230 V AC typical
    50 ms 125 V DC typical
    Display Type Monochrome graphic LCD
    Display Resolution 128 x 128 pixels
    Sampling rate 128 samples/cycle
    Measurement current 50…10000 mA
    Analogue input type Voltage (impedance 5 MOhm)
    Current (impedance <= 0.3 mOhm)
    Measurement voltage 20…400 V AC 45...65 Hz between phase and neutral
    20…828 V AC 45...65 Hz between phases
    Frequency measurement range 45…65 Hz
    Number of inputs 4 digital
    Measurement accuracy Apparent power +/- 0.5 %
    Frequency +/- 0.05 %
    Active energy +/- 0.2 %
    Reactive energy +/- 1 %
    Active power +/- 0.2 %
    Voltage +/- 0.1 %
    Power factor +/- 0.005
    Current +/- 0.15 %
    Reactive power +/- 1 %
    Accuracy class Class 0.2S active energy IEC 62053-22
    Number of Outputs 2 digital
    Information displayed Tariff 8)
    Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
    JBUS
    Modbus TCP/IP 10/100 Mbit/s 2500 V
    Ethernet Modbus TCP/IP daisy chain
    BACnet IP
    DNP3 over ethernet
    Communication port support RS485
    ETHERNET
    communication gateway Ethernet/serial
    data recording Event logs
    Maintenance logs
    Min/max of instantaneous values
    Data logs
    Alarm logs
    Time stamping
    Memory capacity 1.1 MB
    Web services Alarm notification by e-mail
    Web server
    Diagnostic via predefined web pages
    Real time viewing of data
    Ethernet service SNTP client
    SNMP-Traps
    Connections - terminals Voltage circuit screw terminal block4
    Control circuit screw terminal block2
    Current transformer screw terminal block6
    RS485 link screw terminal block4
    Digital input screw terminal block8
    Digital output screw terminal block4
    Ethernet network RJ45 connector2
    Mounting Mode Flush-mounted
    Mounting support Framework
    Standards EN 50470-3
    IEC 61557-12:2015
    IEC 62053-22:2020
    IEC 62053-24
    IEC 60529
    EN 50470-1
    UL 61010-1
    IEC 62053-23:2020
    IEC 62052-11:2020
    IEC 62052-31:2015
    Product certifications CE IEC 61010-1
    CULus UL 61010-1
    Width 3.78 in (96 mm)
    Depth 2.83 in (72 mm)
    Height 3.78 in (96 mm)
    Net Weight 15.87 oz (450 g)
    Environment
    Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2
    Conducted RF disturbances level 3 conforming to IEC 61000-4-6
    Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
    Conducted and radiated emissions class B conforming to EN 55022
    Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
    Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
    Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
    Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
    Surge immunity test level 4 conforming to IEC 61000-4-5
    Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
    IP degree of protection Display IP54 IEC 60529
    Rear IP30 IEC 60529
    Relative humidity 5…95 % 122 °F (50 °C) non-condensing
    Pollution degree 2
    Ambient air temperature for operation -13…158 °F (-25…70 °C)
    Ambient Air Temperature for Storage -40…185 °F (-40…85 °C)
    Operating altitude <= 9842.52 ft (3000 m)
bottom of page