METSEPM5330 power meter, modbus, up to 31st Harmonic, 256KB 2DI/2DO 35 alarms
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 31st Harmonic. Include 256 kiloBytes of memory for two fixed parameters, active and reactive energy. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has two digital inputs or digital outputs, configurable, and dual relay outputs. There are 35 configurable alarms and it supports four tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 15.2 onces (430 g).
Specifications
Main Range PowerLogic Product name PowerLogic PM5000 device short name PM5330 Product or Component Type Power meter Complementary Power quality analysis Up to the 31st harmonic Device Application Power monitoring
Multi-tariffType of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive powersupply voltage 90...450 V AC 45...65 Hz
100...300 V DCNetwork Frequency 50 Hz
60 HzLine Rated Current 1 A
5 Atype of network 3P + N
3P
1P + NMaximum power consumption in VA 11 VA 415 V Ride-through time 80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typicalDisplay Type Monochrome graphic LCD Display Resolution 128 x 128 pixels Sampling rate 64 samples/cycle Measurement current 5…8500 mA Analogue input type Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)Measurement voltage 35…760 V AC 45...65 Hz between phases
20…400 V AC 45...65 Hz between phase and neutralFrequency measurement range 45…65 Hz Number of inputs 2 digital Measurement accuracy Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %Accuracy class Class 0.5S active energy IEC 62053-22 Number of Outputs 2 relay
2 digitalInformation displayed Tariff 4) Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
JBUSCommunication port support RS485 data recording Maintenance logs
Time stamping
Alarm logs
Data logs
Min/max of instantaneous values
Event logsMemory capacity 256 kB Connections - terminals Voltage circuit screw terminal block4
Control circuit screw terminal block2
Current transformer screw terminal block6
Input/output circuit screw terminal block6
Relay output screw terminal block4
Ethernet network RJ45 connectorMounting Mode Flush-mounted Mounting support Framework Product certifications CE IEC 61010-1
CULus UL 61010-1Width 3.78 in (96 mm) Depth 2.83 in (72 mm) Height 3.78 in (96 mm) Net Weight 15.17 oz (430 g) Environment Electromagnetic compatibility Conducted and radiated emissions class B conforming to EN 55022
Immunity to conducted disturbances - test level: 150 kHz...80 MHz level 4 conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test level 3 conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test level 4 conforming to IEC 61000-4-3
Voltage dips and interruptions immunity test class B conforming to IEC 61000-4-11
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2IP degree of protection Display IP54 IEC 60529
Rear IP30 IEC 60529Relative humidity 5…95 % 122 °F (50 °C) non-condensing Pollution degree 2 Ambient air temperature for operation -13…158 °F (-25…70 °C) meter Ambient Air Temperature for Storage -40…185 °F (-40…85 °C) Operating altitude 6561.68 ft (2000 m) CAT III
9842.52 ft (3000 m) CAT II