This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to the 31st Harmonic. Include 256 kiloBytes of memory for two fixed parameters, active and reactive energy. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has two digital inputs or digital outputs, configurable, and dual relay outputs. There are 35 configurable alarms and it supports four tariff schedules. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 15.2 onces (430 g).

  • Specifications

    Main
    Range PowerLogic
    Product name PowerLogic PM5000
    device short name PM5330
    Product or Component Type Power meter
    Complementary
    Power quality analysis Up to the 31st harmonic
    Device Application Power monitoring
    Multi-tariff
    Type of measurement Current
    Voltage
    Frequency
    Power factor
    Energy
    Active and reactive power
    supply voltage 90...450 V AC 45...65 Hz
    100...300 V DC
    Network Frequency 50 Hz
    60 Hz
    Line Rated Current 1 A
    5 A
    type of network 3P + N
    3P
    1P + N
    Maximum power consumption in VA 11 VA 415 V
    Ride-through time 80 ms 120 V AC typical
    100 ms 230 V AC typical
    100 ms 415 V AC typical
    50 ms 125 V DC typical
    Display Type Monochrome graphic LCD
    Display Resolution 128 x 128 pixels
    Sampling rate 64 samples/cycle
    Measurement current 5…8500 mA
    Analogue input type Voltage (impedance 5 MOhm)
    Current (impedance <= 0.3 mOhm)
    Measurement voltage 35…760 V AC 45...65 Hz between phases
    20…400 V AC 45...65 Hz between phase and neutral
    Frequency measurement range 45…65 Hz
    Number of inputs 2 digital
    Measurement accuracy Active energy +/- 0.5 %
    Reactive energy +/- 2 %
    Active power +/- 0.5 %
    Apparent power +/- 0.5 %
    Frequency +/- 0.05 %
    Power factor +/- 0.5
    Current +/- 0.5 %
    Voltage +/- 0.5 %
    Apparent energy +/- 0.5 %
    Reactive power +/- 2 %
    Accuracy class Class 0.5S active energy IEC 62053-22
    Number of Outputs 2 relay
    2 digital
    Information displayed Tariff 4)
    Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
    JBUS
    Communication port support RS485
    data recording Maintenance logs
    Time stamping
    Alarm logs
    Data logs
    Min/max of instantaneous values
    Event logs
    Memory capacity 256 kB
    Connections - terminals Voltage circuit screw terminal block4
    Control circuit screw terminal block2
    Current transformer screw terminal block6
    Input/output circuit screw terminal block6
    Relay output screw terminal block4
    Ethernet network RJ45 connector
    Mounting Mode Flush-mounted
    Mounting support Framework
    Product certifications CE IEC 61010-1
    CULus UL 61010-1
    Width 3.78 in (96 mm)
    Depth 2.83 in (72 mm)
    Height 3.78 in (96 mm)
    Net Weight 15.17 oz (430 g)
    Environment
    Electromagnetic compatibility Conducted and radiated emissions class B conforming to EN 55022
    Immunity to conducted disturbances - test level: 150 kHz...80 MHz level 4 conforming to IEC 61000-4-6
    Electrical fast transient/burst immunity test level 3 conforming to IEC 61000-4-4
    Radiated radio-frequency electromagnetic field immunity test level 4 conforming to IEC 61000-4-3
    Voltage dips and interruptions immunity test class B conforming to IEC 61000-4-11
    Limits for harmonic current emissions class A conforming to IEC 61000-3-2
    Electrostatic discharge level 4 conforming to IEC 61000-4-2
    Conducted RF disturbances level 3 conforming to IEC 61000-4-6
    Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
    Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6
    Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
    Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
    Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
    Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3
    Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2
    IP degree of protection Display IP54 IEC 60529
    Rear IP30 IEC 60529
    Relative humidity 5…95 % 122 °F (50 °C) non-condensing
    Pollution degree 2
    Ambient air temperature for operation -13…158 °F (-25…70 °C) meter
    Ambient Air Temperature for Storage -40…185 °F (-40…85 °C)
    Operating altitude 6561.68 ft (2000 m) CAT III
    9842.52 ft (3000 m) CAT II