METSEPM5110 power meter, modbus, up to 15th Harmonic, 1DO 33 alarms
This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).
Specifications
Main Range PowerLogic Product name PowerLogic PM5000 device short name PM5110 Product or Component Type Power meter Complementary Power quality analysis Up to the 15th harmonic Device Application Power monitoring Type of measurement Current
Voltage
Frequency
Power factor
Energy
Active and reactive powersupply voltage 90...450 V AC 45...65 Hz
100...300 V DCNetwork Frequency 50 Hz
60 HzLine Rated Current 1 A
5 Atype of network 1P + N
3P + N
3PMaximum power consumption in VA 11 VA 415 V Ride-through time 80 ms 120 V AC typical
100 ms 230 V AC typical
100 ms 415 V AC typical
50 ms 125 V DC typicalDisplay Type Monochrome graphic LCD Display Resolution 128 x 128 pixels Sampling rate 64 samples/cycle Measurement current 50…8500 mA Analogue input type Voltage (impedance 5 MOhm)
Current (impedance <= 0.3 mOhm)Measurement voltage 35…760 V AC 45...65 Hz between phases
20…440 V AC 45...65 Hz between phase and neutralFrequency measurement range 45…65 Hz Number of inputs 0 Measurement accuracy Active energy +/- 0.5 %
Reactive energy +/- 2 %
Active power +/- 0.5 %
Apparent power +/- 0.5 %
Frequency +/- 0.05 %
Power factor +/- 0.5
Current +/- 0.5 %
Voltage +/- 0.5 %
Apparent energy +/- 0.5 %
Reactive power +/- 2 %Accuracy class Class 0.5S active energy IEC 62053-22 Number of Outputs 1 digital Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
JBUSCommunication port support RS485 data recording Time stamping
Min/max of instantaneous valuesConnections - terminals Voltage circuit screw terminal block4
Control circuit screw terminal block2
Current transformer screw terminal block6
Input/output circuit screw terminal block6
RS485 link screw terminal block4Mounting Mode Flush-mounted Mounting support Framework Product certifications CE IEC 61010-1
CULus UL 61010-1Width 3.78 in (96 mm) Depth 2.83 in (72 mm) Height 3.78 in (96 mm) Net Weight 13.40 oz (380 g) Environment Electromagnetic compatibility Voltage dips and interruptions immunity test class A conforming to IEC 61000-4-11
Limits for harmonic current emissions class A conforming to IEC 61000-3-2
Electrostatic discharge level 4 conforming to IEC 61000-4-2
Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Magnetic field at power frequency level 4 conforming to IEC 61000-4-8
Conducted and radiated emissions class B conforming to EN 55022
Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Surge immunity test conforming to IEC 61000-4-5
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11IP degree of protection Display IP54 IEC 60529
Rear IP30 IEC 60529Relative humidity 5…95 % 122 °F (50 °C) non-condensing Pollution degree 2 Ambient air temperature for operation -13…158 °F (-25…70 °C) meter
-4…158 °F (-20…70 °C) display
-13…-4 °F (-25…-20 °C) with reduced performance) displayAmbient Air Temperature for Storage -40…185 °F (-40…85 °C) Operating altitude 6561.68 ft (2000 m) CAT III