METSECT5MD050 Current transformer tropicalised DIN mount 500 5 cables d. 40
$128.00Price
This current transformer, tropicalised for busbar and cable, has a line rated current of 500 A and a secondary current rating of 5 A. This current transformer allow a maximum cable outer diameter of 40 mm. Compatible with a double output for bar: 50.5 mm x 12.5 mm or 40.5 mm x 20.5 mm. Burden and accuracy class as follows: class 0.5 maximum power: 4 VA, class 1 maximum power: 6 VA.
Specifications
Main Range PowerLogic Product name CT Product or component type Current transformer Secondary current 5 A Accuracy class Class 0.5 at 4 VA
Class 1 at 6 VA[In] rated current 500 A Complementary current transformer type Tropicalised for busbar and cable current transformer ratio 500/5 [Ith] conventional free air thermal current 30 kA dynamic withstand current 2.5 Ith Maximum safety factor 5 [Ue] rated operational voltage < 720 V AC 50/60 Hz [Ui] rated insulation voltage 3 kV Mounting mode Insulated locking screw
Clip-on
By screwsmounting support DIN rail
Busbar
Mounting plateWidth 70 mm outside: Height 95 mm outside: Depth 45 mm frame:
65 mm total:Diameter 40 mm Net weight 0.329 kg [Uimp] rated impulse withstand voltage 3 kV Electrical insulation class Class B Cable outer diameter 40 mm Opening of bars 50.5 x 12.5
40.5 x 20.5Sealing Without Environment standards VDE 0414
IEC 61869-2product certifications CE IP degree of protection IP20 Relative humidity 0…95 % Ambient air temperature for operation -25…60 °C