LV563505 circuit breaker, EasyPact CVS630F, 36kA at 415VAC, 630A, ETS 2.3
This device is a rated current 630A circuit breaker from EasyPact CVS630F. The rated breaking capacity(Ics) is 36kA at 415VAC,and complete range with Ics=100%Icu. The version of breaker is 3poles frame with detection on 3poles, also accompanied ETS 2.3 trip unit for electronic protection. It is conformed to standard IEC60947-2 for circuit breakers part. This device is certified for operation in pollution degree III environment as defined IEC60947-1& IEC60664-1, and respected for RoHs requirement as european environment directive EC/2002/95. It can be mounted by blackplate or Din rail,also through the door of class II switchboard without downgrading switchboard insulation. The front of toggle offers IP40 protection, but when it is equiped extended rotary handle inside the switchboard, additional IP54 protection degree for extended rotary handle. This series have slots for electrical auxiliaries(MN/MX/OF/SD),depending on the type of trip unit if rotary handle installed. The fixed dimension is 140mm width.255mm height,110mm depth,
Specifications
Main Range EasyPact Range of product EasyPact CVS400...630 Product name EasyPact CVS Device short name CVS630F Product or component type Circuit breaker Device application Distribution poles description 3P Protected poles description 3D Earth leakage protection (Vigi add on) Without [In] rated current 630 A at 40 °C Network type AC Utilisation category Category A [Icu] Breaking capacity 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2Trip unit name ETS 2.3 Trip unit technology Electronic Trip unit rating 630 A at 40 °C Protection type Short time short-circuit protection
Instantaneous short-circuit protection
Overload protection (long time)Complementary [Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2 Network frequency 50/60 Hz Breaking capacity code F [Ics] rated service breaking capacity 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2Mechanical durability 15000 cycles Electrical durability 4000 cycles 415 V In conforming to IEC 60947-2 Trip unit protection functions LSoI Control type Toggle Long time pick-up adjustment type Ir Adjustable 9 settings Long time pick-up adjustment range 250...630 A Long time delay adjustment type Fixed [tr] long-time delay adjustment range 5.5 s at 7.2 x Ir
8 s at 6 x Ir
200 s at 1.5 x Irthermal memory Yes Short-time pick-up adjustment type Isd Adjustable 9 settings [Isd] short-time pick-up adjustment range 1.5...10 x Ir Short-time delay adjustment type Fixed Instantaneous pick-up adjustment type Ii Fixed instantaneous pick-up adjustment range 11 x In Contact position indicator Yes Mounting support Backplate Mounting mode Fixed Upside connection Front downside connection Front Connections - terminals Screw connection Connection pitch 45 mm Compatibility code CVS630 Width 140 mm Depth 110 mm Height 255 mm Net weight 5.2 kg