top of page
LV563505 circuit breaker, EasyPact CVS630F, 36kA at 415VAC, 630A, ETS 2.3

LV563505 circuit breaker, EasyPact CVS630F, 36kA at 415VAC, 630A, ETS 2.3

$530.00Price

This device is a rated current 630A circuit breaker from EasyPact CVS630F. The rated breaking capacity(Ics) is 36kA at 415VAC,and complete range with Ics=100%Icu. The version of breaker is 3poles frame with detection on 3poles, also accompanied ETS 2.3 trip unit for electronic protection. It is conformed to standard IEC60947-2 for circuit breakers part. This device is certified for operation in pollution degree III environment as defined IEC60947-1& IEC60664-1, and respected for RoHs requirement as european environment directive EC/2002/95. It can be mounted by blackplate or Din rail,also through the door of class II switchboard without downgrading switchboard insulation. The front of toggle offers IP40 protection, but when it is equiped extended rotary handle inside the switchboard, additional IP54 protection degree for extended rotary handle. This series have slots for electrical auxiliaries(MN/MX/OF/SD),depending on the type of trip unit if rotary handle installed. The fixed dimension is 140mm width.255mm height,110mm depth,

Only 4 left in stock
  • Specifications

    Main
    Range EasyPact
    Range of product EasyPact CVS400...630
    Product name EasyPact CVS
    Device short name CVS630F
    Product or component type Circuit breaker
    Device application Distribution
    poles description 3P
    Protected poles description 3D
    Earth leakage protection (Vigi add on) Without
    [In] rated current 630 A at 40 °C
    Network type AC
    Utilisation category Category A
    [Icu] Breaking capacity  40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Trip unit name ETS 2.3
    Trip unit technology Electronic
    Trip unit rating 630 A at 40 °C
    Protection type Short time short-circuit protection
    Instantaneous short-circuit protection
    Overload protection (long time)
    Complementary
    [Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
    Network frequency 50/60 Hz
    Breaking capacity code F
    [Ics] rated service breaking capacity 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    23 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 15000 cycles
    Electrical durability 4000 cycles 415 V In conforming to IEC 60947-2
    Trip unit protection functions LSoI
    Control type Toggle
    Long time pick-up adjustment type Ir Adjustable 9 settings
    Long time pick-up adjustment range 250...630 A
    Long time delay adjustment type Fixed
    [tr] long-time delay adjustment range 5.5 s at 7.2 x Ir
    8 s at 6 x Ir
    200 s at 1.5 x Ir
    thermal memory Yes
    Short-time pick-up adjustment type Isd Adjustable 9 settings
    [Isd] short-time pick-up adjustment range 1.5...10 x Ir
    Short-time delay adjustment type Fixed
    Instantaneous pick-up adjustment type Ii Fixed
    instantaneous pick-up adjustment range 11 x In
    Contact position indicator Yes
    Mounting support Backplate
    Mounting mode Fixed
    Upside connection Front
    downside connection Front
    Connections - terminals Screw connection
    Connection pitch 45 mm
    Compatibility code CVS630
    Width 140 mm
    Depth 110 mm
    Height 255 mm
    Net weight 5.2 kg
bottom of page