LC1D25M7 IEC contactor, TeSys Deca, nonreversing, 25A, 15HP at 480VAC
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 25A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 7.5HP at 200-208VAC, 7.5HP at 240VAC, 15HP at 480VAC and 20HP at 600VAC three phase. Contactor is also rated for 2HP at 115VAC and 3HP at 240VAC single phase. When used with a 480VAC up to 60A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 60A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.35 inches tall, 1.77 inches wide and 3.62 inches deep. It weighs 0.82 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.
Specifications
Main Range of Product TeSys Deca Product or Component Type Contactor Device short name LC1D contactor application Motor control
Resistive loadUtilisation category AC-1
AC-3
AC-4
AC-3ePoles description 3P [Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC[Ie] rated operational current 25 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
40 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit[Uc] control circuit voltage 220 V AC 50/60 Hz Complementary Motor power kW 5.5 kW at 220...230 V AC 50/60 Hz (AC-3)
11 kW at 380...400 V AC 50/60 Hz (AC-3)
11 kW at 415...440 V AC 50/60 Hz (AC-3)
15 kW at 500 V AC 50/60 Hz (AC-3)
15 kW at 660...690 V AC 50/60 Hz (AC-3)
5.5 kW at 400 V AC 50/60 Hz (AC-4)
5.5 kW at 220...230 V AC 50/60 Hz (AC-3e)
11 kW at 380...400 V AC 50/60 Hz (AC-3e)
11 kW at 415...440 V AC 50/60 Hz (AC-3e)
15 kW at 500 V AC 50/60 Hz (AC-3e)
15 kW at 660...690 V AC 50/60 Hz (AC-3e)Maximum Horse Power Rating 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
2 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 3 phase motors
15 hp at 460/480 V AC 50/60 Hz for 3 phase motors
20 hp at 575/600 V AC 50/60 Hz for 3 phase motors
7.5 hp at 200/208 V AC 50/60 Hz for 3 phase motorsCompatibility code LC1D Pole contact composition 3 NO Protective cover With [Ith] conventional free air thermal current 10 A (at 140 °F (60 °C)) for signalling circuit
40 A (at 140 °F (60 °C)) for power circuitIrms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
450 A at 440 V for power circuit conforming to IEC 60947Rated breaking capacity 450 A at 440 V for power circuit conforming to IEC 60947 [Icw] rated short-time withstand current 240 A 104 °F (40 °C) - 10 s for power circuit
380 A 104 °F (40 °C) - 1 s for power circuit
50 A 104 °F (40 °C) - 10 min for power circuit
120 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuitAssociated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
63 A gG at <= 690 V coordination type 1 for power circuit
40 A gG at <= 690 V coordination type 2 for power circuitAverage impedance 2 mOhm - Ith 40 A 50 Hz for power circuit Power dissipation per pole 3.2 W AC-1
1.25 W AC-3
1.25 W AC-3e[Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V ULOvervoltage category III Pollution degree 3 [Uimp] rated impulse withstand voltage 6 kV IEC 60947