top of page
LC1D09M7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA

LC1D09M7 IEC contactor, TeSys Deca, nonreversing, 9A, 5HP at 480VAC, up to 100kA

$39.00Price

TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 9A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200-208VAC, 25HP at 240VAC, 60HP at 480VAC and 60HP at 600VAC three phase. Contactor is also rated for 7.5HP at 115VAC and 15HP at 240VAC single phase. When used with a 480VAC up to 35A circuit breaker, this contactor can have a SCCR up to 85kA. When used with up to a 600VAC 25A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 220 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 3.15 inches tall, 1.77 inches wide and 3.39 inches deep. It weighs 0.71 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.

Only 8 left in stock
  • Specifications

    Main
    Range of Product TeSys Deca
    Product or Component Type Contactor
    Device short name LC1D
    contactor application Motor control
    Resistive load
    Utilisation category AC-4
    AC-3
    AC-1
    AC-3e
    Poles description 3P
    [Ue] rated operational voltage Power circuit <= 690 V AC 25...400 Hz
    Power circuit <= 300 V DC
    [Ie] rated operational current 9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
    25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
    9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
    [Uc] control circuit voltage 220 V AC 50/60 Hz
    Complementary
    Motor power kW 2.2 kW at 220...230 V AC 50/60 Hz (AC-3)
    4 kW at 380...400 V AC 50/60 Hz (AC-3)
    4 kW at 415...440 V AC 50/60 Hz (AC-3)
    5.5 kW at 500 V AC 50/60 Hz (AC-3)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3)
    2.2 kW at 400 V AC 50/60 Hz (AC-4)
    2.2 kW at 220...230 V AC 50/60 Hz (AC-3e)
    4 kW at 380...400 V AC 50/60 Hz (AC-3e)
    4 kW at 415...440 V AC 50/60 Hz (AC-3e)
    5.5 kW at 500 V AC 50/60 Hz (AC-3e)
    5.5 kW at 660...690 V AC 50/60 Hz (AC-3e)
    Maximum Horse Power Rating 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 200/208 V AC 50/60 Hz for 3 phase motors
    2 hp at 230/240 V AC 50/60 Hz for 3 phase motors
    5 hp at 460/480 V AC 50/60 Hz for 3 phase motors
    7.5 hp at 575/600 V AC 50/60 Hz for 3 phase motors
    0.33 hp at 115 V AC 50/60 Hz for 1 phase motors
    Compatibility code LC1D
    Pole contact composition 3 NO
    Protective cover With
    [Ith] conventional free air thermal current 25 A (at 140 °F (60 °C)) for power circuit
    10 A (at 140 °F (60 °C)) for signalling circuit
    Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947
    140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
    Rated breaking capacity 250 A at 440 V for power circuit conforming to IEC 60947
    [Icw] rated short-time withstand current 105 A 104 °F (40 °C) - 10 s for power circuit
    210 A 104 °F (40 °C) - 1 s for power circuit
    30 A 104 °F (40 °C) - 10 min for power circuit
    61 A 104 °F (40 °C) - 1 min for power circuit
    100 A - 1 s for signalling circuit
    120 A - 500 ms for signalling circuit
    140 A - 100 ms for signalling circuit
    Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1
    25 A gG at <= 690 V coordination type 1 for power circuit
    20 A gG at <= 690 V coordination type 2 for power circuit
    Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
    Power dissipation per pole 1.56 W AC-1
    0.2 W AC-3
    0.2 W AC-3e
    [Ui] rated insulation voltage Power circuit 690 V IEC 60947-4-1
    Power circuit 600 V CSA
    Power circuit 600 V UL
    Signalling circuit 690 V IEC 60947-1
    Signalling circuit 600 V CSA
    Signalling circuit 600 V UL
    Overvoltage category III
    Pollution degree 3
    [Uimp] rated impulse withstand voltage 6 kV IEC 60947
    Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
    Mechanical durability 15 Mcycles
    Electrical durability 0.6 Mcycles 25 A AC-1 <= 440 V
    2 Mcycles 9 A AC-3 <= 440 V
    2 Mcycles 9 A AC-3e <= 440 V
    Control circuit type AC 50/60 Hz standard
    Coil technology Without built-in suppressor module
bottom of page