GV2ME01 Manual Starter and Protector, thermal magnetic circuit protector
$135.00Price
TeSys GV motor circuit breaker, 3 poles (3P), 0.16A/690V, for 3-phase motor applications less than 0.06kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.1-0.16A, magnetic tripping at 9xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Only 4 left in stock
Specifications
Main Range TeSys Deca Product name TeSys GV2
TeSys DecaProduct or Component Type Motor circuit breaker Device short name GV2ME Device Application Motor protection Trip unit technology Thermal-magnetic Complementary Poles description 3P Network type AC Utilisation category Category A IEC 60947-2
AC-3 IEC 60947-4-1
AC-3e IEC 60947-4-1Network frequency 50/60 Hz IEC 60947-4-1 Fixing mode 35 mm symmetrical DIN rail clipped
Panel screwed with adaptor plate)Breaking capacity 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
100 kA Icu 440 V AC 50/60 Hz IEC 60947-2
100 kA Icu 500 V AC 50/60 Hz IEC 60947-2
100 kA Icu 690 V AC 50/60 Hz IEC 60947-2[Ics] rated service short-circuit breaking capacity 100 % 230/240 V AC 50/60 Hz IEC 60947-2
100 % 400/415 V AC 50/60 Hz IEC 60947-2
100 % 440 V AC 50/60 Hz IEC 60947-2
100 % 500 V AC 50/60 Hz IEC 60947-2
100 % 690 V AC 50/60 Hz IEC 60947-2Control Type Push-button Line Rated Current 0.16 A Thermal protection adjustment range 0.1…0.16 A IEC 60947-4-1 Magnetic tripping current 1.5 A [Ith] conventional free air thermal current 0.16 A IEC 60947-4-1 [Ue] rated operational voltage 690 V AC 50/60 Hz IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2 Phase failure sensitivity Yes IEC 60947-4-1 Suitability for isolation Yes IEC 60947-1 § 7-1-6 Power dissipation per pole 2.5 W Mechanical durability 100000 cycles Electrical durability 100000 cycles AC-3 415 V In
100000 cycles AC-3e 415 V InRated duty Continuous IEC 60947-4-1 Tightening torque 15.05 lbf.in (1.7 N.m) screw clamp terminal Width 1.77 in (45 mm) Height 3.50 in (89 mm) Depth 3.09 in (78.5 mm) Net Weight 0.57 lb(US) (0.26 kg) color Dark grey Environment Standards EN/IEC 60947-2
EN/IEC 60947-4-1Product Certifications CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
RINA
DNV-GL
UKCAIK degree of protection IK04 IP degree of protection IP20 IEC 60529 Climatic withstand IACS E10 Ambient Air Temperature for Storage -40…176 °F (-40…80 °C) Fire resistance 1760 °F (960 °C) IEC 60695-2-11 Ambient air temperature for operation -4…140 °F (-20…60 °C) Mechanical robustness Shocks 30 Gn for 11 ms
Vibrations 5 Gn, 5...150 HzOperating altitude 6561.68 ft (2000 m)