GB2DB12 TeSys GB2 thermal magnetic circuit protector, 2 P, 6 A, Id = 83 A
$85.00Price
TeSys GB circuit breaker, 2 poles (2P), 6A/415V, for the protection of industrial equipment control circuits. It provides thermal magnetic protection with a magnetic tripping level at 83A (13 In) and breaking capacity Icu 1.5kA@415V. It can also be used for protection of DC loads up to 6A/48V DC-13 with a breaking capacity Icu 1.5kA@24V. Compact device (30mm wide), mounting on 35mm DIN-rail, control by toggle lever (start-stop guaranteed for 8000 cycles). Sold in lots of 3 units. It conforms to IEC 60947-1 and IEC 60947-2, Green Premium product (RoHS/REACh).
Only 5 left in stock
Specifications
Main Range TeSys Product name TeSys GB2 Device short name GB2 Product or Component Type Circuit breaker Device Application Control Poles description 2P Network type AC/DC Utilisation category Category A IEC 60947-2
DC-12 IEC 60947-5-1
DC-13 IEC 60947-5-1Network frequency 50/60 Hz IEC 60947-2 Breaking capacity 3 kA Icu 110 V AC 50/60 Hz IEC 60947-2
1.5 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
1.5 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
1.5 kA Icu 24 V DC IEC 60947-2
1 kA Icu 48 V DC IEC 60947-2[Ics] rated service short-circuit breaking capacity 75 % 110 V AC 50/60 Hz IEC 60947-2
75 % 230/240 V AC 50/60 Hz IEC 60947-2
75 % 400/415 V AC 50/60 Hz IEC 60947-2Trip unit technology Thermal-magnetic Magnetic tripping current 83 A Complementary Mounting Mode By clips Mounting Support Rail
PlateMounting position Horizontal
VerticalControl Type Toggle Line Rated Current 6 A [Ue] rated operational voltage 415 V AC 50/60 Hz IEC 60947-2
48 V DC[Uimp] rated impulse withstand voltage 4 kV IEC 60947-2 Power dissipation per pole 2 W Mechanical durability 8000 cycles Electrical durability 8000 cycles Connections - terminals Connector 1 0.00…0.01 in² (0.75…6 mm²)solid without cable end
connector 2 0.00…0.01 in² (0.75…4 mm²)solid without cable end
connector 1 0.00…0.01 in² (0.75…4 mm²)flexible with cable end
connector 2 0.00…0.00 in² (0.75…2.5 mm²)flexible with cable endTightening torque 10.62 lbf.in (1.2 N.m) connector Mechanical robustness Shocks 22 Gn for 20 ms IEC 60068-2-27
Vibrations 5 Gn, 5...110 Hz IEC 60068-2-6Quantity per Set Set of 3 9 mm pitches 4 Height 2.91 in (74 mm) Width 1.18 in (30 mm) Depth 2.76 in (70 mm) Net Weight 0.25 lb(US) (0.115 kg) Environment Standards EN/IEC 60947-1
EN/IEC 60947-2Protective treatment TC IP degree of protection IP20 IEC 60529 Ambient air temperature for operation -4…140 °F (-20…60 °C) Ambient Air Temperature for Storage -40…176 °F (-40…80 °C) Fire resistance 1760 °F (960 °C) IEC 60695-2-1 Operating altitude 9842.52 ft (3000 m)